Free energy flat stacked heat exchange technology
white paper
Flat-Stack Heat Exchange Technology Whitepaper
Foshan Ziyou Energy Electric Co., Ltd.
Foshan Free Energy Electrical Co., Ltd.
July 2026 | Version 1.0
[Internal Document]• Do not distribute.
Chapter 1 Introduction and Background
1.1 Technological Evolution of the Gas-fired Boiler Industry
1.2 Bottlenecks of Fully Premixed Condensation Technology
1.3 The Birth of Flat Stacking Technology
Chapter Two Flat stacking technology principle
2.1 Geometric Optimization: From Circular Tubes to Flat Square Tubes
2.2 Three-dimensional stacked structure design
2.3 Principle of Maximizing Heat Transfer Area
2.4 Selection of 316 Stainless Steel Material
Chapter Three Combustion and Control System
3.1 Ample burner technology
3.2 1:10 Precision Premixed Combustion
3.3 The electric proportional valve is infinitely adjustable.
Chapter Four Performance test data
4.1 Thermal efficiency test
4.2 Emissions Testing
4.3 Partial Load Performance
4.4 Durability and Reliability
Chapter Five Compared with traditional technologies
5.1 Round Tube Heat Exchanger vs. Flat Square Stacked Heat Exchanger
5.2 Comparison of Life Cycle Costs
5.3 Comparison of Environmental Benefits
Chapter Six Application Scenarios and Cases
Chapter Seven Technology Outlook
appendix
Gas-fired boiler technology has undergone three major transformations in the past four decades:
·First generation ((1980s-2000s): Traditional cast iron/steel boilers, with a thermal efficiency of 85-90% and a flue gas temperature of 180-250℃, resulting in a significant loss of heat energy with the flue gas.
·Second generation ((2000s-2015s): Condensing boilers, which improve thermal efficiency to 95-103% by recovering the latent heat of flue gas, and reduce flue gas temperature to 50-80℃.
·Third generation ((2015s to present): Fully premixed condensing boilers, precisely controlling the air-fuel ratio, achieving a thermal efficiency exceeding 106%, and reducing NOx emissions to [amount missing].20-30mg/m³
However, the industryAfter the "fully premixed" approach, the technology became homogenized. Brands converged on combustion control, and the real space for differentiation returned to the heat exchanger structure itself—which is precisely the direction for breakthroughs in flat-panel stacking technology.
Currently, fully premixed condensing boilers on the market generally adopt...The "circular tube heat exchanger" structure has the following physical bottlenecks:
bottleneck | physical reasons | Impact on customers |
Limited heat exchange area | The arrangement of circular tubes has natural gaps, resulting in low space utilization.60-70% | There is limited room for improvement in thermal efficiency, making breakthroughs difficult.108% |
Size and power contradiction | To increase power, the number or length of the cylindrical tubes must be increased, resulting in a linear increase in volume. | High-power boilers require a large footprint and have high infrastructure costs. |
Local hotspots | Flame between round tubesUneven flue gas distribution, resulting in excessively high local temperatures. | Increased NOx formation leads to uneven thermal stress in heat exchange tubes and a shortened lifespan. |
Condensation corrosion risk | Condensate accumulates at the bottom of the round pipe.304 stainless steel has insufficient acid resistance | Pitting and perforation occur after 3-5 years, resulting in high maintenance costs. |
Partial load efficiency degradation | Poor flame stability and runaway air-fuel ratio at low loads | The actual operating efficiency is far lower than the nameplate efficiency. |
Starting from the fundamental issue of heat exchanger geometry, the Free Energy R&D team proposed a brand-new technical approach: replacing round tubes with flat square tubes, and achieving bidirectional extreme optimization of maximizing heat exchange area and minimizing volume through precise three-dimensional stacking.
The core idea of the flat stacking technology is: since the physical upper limit of heat exchange efficiency is determined by the heat exchange area, we can break through this upper limit through geometric structure.—It's not about adding more pipes, but about making every inch of space a heat exchange surface.
After three years of research and development and hundreds of trialsThrough CFD simulation optimization and prototype testing, Free Energy has successfully moved the flat stacking technology from the laboratory to industrialization, achieving industry-leading performance with thermal efficiency >108%, NOx <30mg/m³, and water volume <30L.
The core performance indicators of a heat exchanger are"Heat transfer area per unit volume" – that is, how much heat transfer surface can be arranged in a finite space. This is a purely geometric problem.
Geometric limitations of circular tubes:
·When circular tubes are arranged, there is a distance between the tubes."Dead zone gap" - the gap between the four round tubes cannot be utilized.
·The theoretical maximum value of the space fill ratio (close-packed hexagonal) of a circular tube is:90.7%, but only 60-70% in actual projects.
·For the same perimeter, a circle has the largest area, but heat exchangers require...Maximize the "surface area/perimeter ratio," not the "area/perimeter ratio."
Geometric advantages of flat square tubes:
·The rectangular cross-section of the flat square tubes allows for close arrangement without any dead angles or gaps, resulting in near-perfect space utilization.100%
·For the same perimeter, the surface area (heat transfer area) of a flat square tube is larger than that of a round tube.20-30% – This is determined by geometry, not by the process.
·The aspect ratio of the flat square tube is adjustable, allowing for optimization of the heat exchange area ratio for different operating conditions.
Round tube:A_circle = pi * D * L (D=diameter, L=pipe chief)
Flat square tube:A_flat = 2*(a+b)*L (a=width, b=high)
Equal perimeterpi*D = 2*(a+b)At that time, the heat exchange area of the flat square tube= Circular tube heat exchange area
However, flat square tubes can be stacked tightly, improving space utilization.40-60%Increased overall heat exchange area2-3double
Flat stacking is not simpleIt's not simply "stacked flat square tubes together," but a sophisticated three-dimensional arrangement system:
·Flue gas side (outer side): Uniform flue gas channels are formed between the flat square tubes, and the flue gas flows through the heat exchange surface in a laminar flow manner, resulting in a high heat transfer coefficient.
·Water side (inner side): The internal water flow channels of the flat rectangular tube are designed as multiple channels in parallel, and the flow velocity is controlled at...1.5-2.0 m/s self-cleaning range
·Hot and cold medium ratio: the heat exchange area on the flue gas side and the heat exchange area on the water side are calculated according to...A precise 1:1 ratio ensures balanced heat exchange on both sides.
·Counter-current design: flue gas flows from top to bottom, while water flows from bottom to top, forming a full counter-current heat exchange to maximize the logarithmic mean temperature difference.LMTD)
Stacking process parameters:
parameter | numerical values | illustrate |
Flat square tube specifications | 30mm x 10mm x 1.0mm | Aspect Ratio3:1, balancing strength and heat exchange area |
Pipe gap | 2.0mm (smoke side) | Optimize flue gas flow resistance and heat transfer coefficient |
Stacking layers | 8-12 layers (single module) | Adjust according to power level |
single module heat exchange area | 8-15 m² | For the same power, it is the traditional round tube.2-3 times |
Welding method | Laser welding+ 100% helium leak detection | The weld strength is higher than that of the base material. |
Flat stacking implementationThe physical mechanism of "maximum heat transfer area under the same power":
Step 1: Advantage of single-tube surface area. For the same perimeter, the surface area of a flat rectangular tube is approximately [missing information - likely a number] times that of a round tube.20%. This is the advantage of basic geometry.
Step Two: Space Utilization Advantages. The dense arrangement of circular tubes...30% of the gap space was wasted; with the flat square tubes arranged closely together with almost no gaps, the space utilization rate increased from 70% to nearly 100%.
Step 3: Stacking density advantage. Flat square tubes can be stacked three-dimensionally to form a multi-layer heat exchange matrix. One unitThe heat exchange area of a 720kW free energy modular boiler can reach 120m², while that of a traditional round tube boiler of the same power is only 40-50m².
Overall effect: The heat exchange area per unit volume is that of a traditional circular tube heat exchanger.2.5-3 times. This is the physical basis for the "largest heat exchange area under the same power".
All free energy flat stacked heat exchangers adoptIt uses 316 stainless steel (06Cr17Ni12Mo2), not the more common 304 stainless steel (06Cr19Ni10). The key difference is:
Performance indicators | 304 stainless steel | 316 stainless steel | Free energy choiceThe reason for 316 |
molybdenum content (For) | 0% | 2-3% | Molybdenum significantly improves resistance to pitting corrosion and combats corrosion in condensate.Cl- ions |
Pitting resistance equivalent (WOOD) | 18-20 | 24-28 | CondensateA pH of 3-5 and a PREN value greater than 24 are required to guarantee a 15-year lifespan. |
Resistance to intergranular corrosion | generally | Excellent (including)Ti/Nb stabilization) | Intergranular corrosion will not occur in the weld heat-affected zone. |
High temperature strength | Below 500℃ | Below 550℃ | The local temperature of the flat square tube can reachAt 450℃, 304 stainless steel is nearing its limit. |
cost | benchmark | Approximately high30% | butThe cost savings from 10 years of maintenance-free maintenance far exceed the difference in material prices. |
Free energy choiceThe rationale behind using 316 stainless steel: Condensing boiler heat exchangers are exposed to acidic condensate water environments for extended periods, and the pitting corrosion resistance of 304 stainless steel is insufficient to support a 15-year design life. Although 316 material costs 30% more, it avoids the risk of pitting and perforation after 3-5 years, resulting in a lower overall lifespan cost.
Ample burner (The Wide-Tolerance Burner is a planar premixed burner independently developed by Free Energy, which is fundamentally different from traditional metal fiber burners:
characteristic | Traditional metal fiber burners | Free energy ample burner | Advantages |
Flame Form | dot/Strip-shaped flame | Blue flat flame | The temperature field is uniform, with no local hot spots. |
Flame temperature | Uneven, localized>1200℃ | Uniform distribution800-900℃ | Thermal typeNOx generation reduced by 80% |
Air-fuel ratio range | narrow(lambda=1.2-1.4) | Width(lambda=1.1-1.6) | Insensitive to fluctuations in gas composition |
backfire risk | higher | Extremely low | Planar flame+Metal fiber structure naturally prevents tempering |
life | 2-3 years | 5 years or more | Uniform temperature field reduces thermal stress fatigue |
Free energy is achieved using a Venturi premixing system.1:10 wide range adjustment ratio:
·Minimum power10%: A single 720kW module can operate stably under a low load of 72kW without extinguishing the flame.
·Maximum power100%: When operating at full load, the air-fuel ratio is precisely controlled at lambda = 1.25 +/- 0.02.
·High efficiency across the entire range:Within the 10%-100% load range, the thermal efficiency fluctuation does not exceed 1 percentage point (107-108%).
The engineering significance of a 1:10 adjustment ratio:
·Traditional boilers experience a sharp drop in efficiency at low loads (e.g.)Efficiency is only 85-90% at 30% load because of flame instability and uncontrolled air-fuel ratio.
·Free energy ample burnerVenturi premixing ensures stable flame performance even at low loads, preventing efficiency degradation.
·In actual operation, the boiler spends most of its time inOperating at 30-70% load, low-load efficiency has a significant impact on annual energy consumption.
Free Energy uses an electric proportional valve to replace the traditional gear regulating valve, achieving stepless continuous regulation of gas flow:
·Adjustment accuracy:0.1% increments, response time <1 second
·Control method:PID closed-loop control adjusts the gas flow rate in real time based on the outlet water temperature.
·Communication interface: SupportedModbus RTU / BACnet MS/TP, can be connected to building automation systems (BAS).
·Safety Redundancy: Dual Solenoid Valves in Series+ High/low gas pressure protection + Flame ionization detection
Infinitely variable adjustmentAdvantages of gear adjustment:
·Gear adjustment (such as)Temperature fluctuations occur when switching between gears (3rd/5th gear), which are noticeable to customers.
·Infinitely variable adjustment"Provide as much heat as you need," with water temperature fluctuations of <0.5℃.
·By integrating with the outdoor temperature compensation curve, climate-compensated intelligent heating can be achieved.
Testing standards:GB 20665-2015 "Minimum Allowable Values of Energy Efficiency and Energy Efficiency Grades for Household Gas-fired Instantaneous Water Heaters and Gas-fired Heating and Hot Water Boilers" and GB/T 10180-2017 "Test Procedures for Thermal Performance of Industrial Boilers"
Test conditions: Inlet water temperature40℃, outlet water temperature 60℃, lower heating value of natural gas 35.0 MJ/m³
Load factor | Smoke temperature(℃) | Condensate volume(kg/h) | Positive balance efficiency(%) | Anti-balance efficiency(%) | Average efficiency(%) |
100% | 48 | 18.2 | 107.8 | 107.5 | 107.7 |
75% | 45 | 16.8 | 108.1 | 107.9 | 108.0 |
50% | 43 | 15.5 | 108.3 | 108.0 | 108.2 |
30% | 41 | 14.1 | 108.5 | 108.2 | 108.4 |
10% | 40 | 12.8 | 108.0 | 107.8 | 107.9 |
Key finding: The free energy flat stacked heat exchanger maintains stable efficiency across the entire load range.107.5-108.5%, efficiency increases instead of decreases at low loads—this is because the flue gas flow rate decreases at low loads, the flue gas stays in the heat exchanger for a longer time, and condensation is more complete.
Testing standards:GB 13271-2014 "Emission Standard of Air Pollutants for Boilers" and DB11/139-2015 "Beijing Municipal Emission Standard of Air Pollutants for Boilers"
pollutants | National standard limits(mg/m³) | Beijing Landmark Limit(mg/m³) | Free energy measurement(mg/m³) | Compliance status |
NOx | 150 (New) | 30 | 25 | Superior to Beijing landmarks |
CO | 100 | — | 15 | Far below national standards |
SO2 | 50 | — | <3 | Natural gas has extremely low sulfur content |
Particulate matter | 20 | — | <5 | Gaseous fuels contain virtually no particulate matter. |
The key to low NOx emissions is that the planar flame temperature of the ample burner is uniform and controlled at 800-900℃, which is far below the formation temperature threshold of thermal NOx (>1300℃), thus inhibiting NOx formation at the source.
Part-load performance is a key indicator for measuring the actual economic efficiency of a boiler's operation. Most boilers in...Efficiency drops sharply below 30% load, but the free energy flat stacked heat exchanger, with its 1:10 control ratio and ample burner, still maintains high efficiency at 10% load.
Comparison of test data (same power)(700kW level)
Load factor | Free energy flat stacking efficiency | Traditional fully premixed condensation efficiency | Traditional cast iron boiler efficiency | Free energy advantage |
100% | 107.7% | 106.5% | 92.0% | +1.2% |
75% | 108.0% | 105.8% | 91.5% | +2.2% |
50% | 108.2% | 103.5% | 89.0% | +4.7% |
30% | 108.4% | 98.0% | 85.0% | +10.4% |
10% | 107.9% | 92.0% | 78.0% | +15.9% |
Conclusion: InAt 30% low load, the free energy efficiency advantage reaches more than 10 percentage points. Considering that the boiler operates at partial load for most of the year, the actual annual energy saving effect far exceeds the efficiency comparison at full load.
The free energy flat stacked heat exchanger has undergone the following durability verifications:
·Accelerated corrosion test: inAfter 2000 hours of continuous operation in an acidic condensate environment with a pH of 3.0, the 316 stainless steel flat square tube showed no pitting or perforation.
·Thermal cycling test:After 1000 cycles of rapid cooling and heating (20℃→90℃→20℃), the weld showed no cracks and passed the hydrostatic test.
·Pressure fatigue test:50,000 cycles of 0-0.6MPa pressure testing showed no leakage or deformation.
·Vibration test: according toGB/T 2423.10 describes sinusoidal sweep vibration; the structure remains intact.
·Actual operation verification: The first batch of installations3000+ modular furnaces, with the longest operating time exceeding 5 years, and zero heat exchanger leakage failures.
Comparison Dimensions | Traditional round tube heat exchanger | Free energy flat stacked heat exchanger | difference |
heat exchanger tube cross section | round | Rectangle (flat square) | For the same perimeter, surface area+20% |
Space utilization | 60-70% | near100% | Seamless and tightly stacked |
Heat transfer area per unit volume | benchmark | 2.5-3 times | Core geometric advantages |
Smoke flow | Turbulence, local dead zones | Laminar flow, uniform distribution | More efficient heat exchange |
Water flow rate control | Difficult to control precisely | 1.5-2.0 m/s self-cleaning flow rate | Anti-scaling design |
Hot and cold area ratio | Normally does not match | 1:1 precision ratio | Heat exchange is balanced on both sides |
Material | 304 stainless steel/aluminum | 316 stainless steel | Acid-resistant condensate |
Design life | 8-10 years | 15 years or more | Material+Dual structural protection |
byTaking a 1400kW (2-ton) heating project as an example, a 10-year TCO comparison:
Cost items | Traditional cast iron boilers | Traditional fully premixed condenser | Free energy flat stack | Free energyvs Traditional Fully Premixed |
Initial investment in equipment | 350,000 | 550,000 | 620,000 | +12.7% |
Installation infrastructure costs | 180,000 | 140,000 | 80,000 | -42.9% |
10 years of gas fees | 5.6 million | 4.48 million | 3.7 million | -17.4% |
10-year maintenance fee | 450,000 | 250,000 | 120,000 | -52.0% |
10-year compliance fee | 300,000 | 150,000 | 0 | -100% |
10-year total cost | 6.88 million | 5.57 million | 4.52 million | -18.8% |
vs. traditional fully premixed energy saving | — | — | 1.05 million | Investment recovery period1.5 years |
Note: Free Energy Compliance Fee is...The number 0 is because the water volume is less than 30L, which does not fall under the category of pressure vessels, and is exempt from annual inspection and boiler operator certification.
index | Traditional cast iron boilers | Traditional fully premixed condenser | Free energy flat stack |
Annual gas consumption(m³) | 160,000 | 128,000 | 105,700 |
YearCO2 emissions (tons) | 346 | 276 | 228 |
YearNOx emissions (kg) | 19.2 | 8.3 | 2.6 |
Carbon trading value(Yuan/Year) | — | — | 2,880 (based on 60 yuan/ton) |
Cumulative CO2 emission reduction over 10 years (tons) | — | — | 1,180 |
Equivalent tree planting(tree) | — | — | 64,500 |
Free energy flat stacked modular furnace is suitable for the following scenarios:
·hotelHotel: 24-hour hot water and heating; long low-load operation time; significant advantage in free energy partial load efficiency.
·Hospitals have extremely high requirements for heating reliability.The N+1 redundancy design ensures that the failure of a single unit does not affect the overall system.
·SchoolOffice building: Intermittent operation, requiring rapid start-up – free energy starts in 3 seconds, while traditional boilers require 30 minutes of preheating.
·factory/Industrial Park: Space is limited; the free energy modular boiler occupies only 1/3 the area of a traditional boiler.
·Bathhouse: High-flow hot water demand, modular parallel connection allows for flexible expansion.
·Replacement of old boilers: Existing boiler rooms have limited space and small free energy volumes can be directly replaced without expansion.
Case 1: Heating system of a five-star hotel+Hot water project
·Project Overview: Building Area45,000㎡, heating and domestic hot water, originally using two 2-ton cast iron boilers.
·Free energy scheme:Six 180kW flat-panel stacked modular furnaces (5 in operation, 1 on standby)
·Operational results: Annual gas cost fromThe cost was reduced from 1.68 million to 1.18 million, saving 500,000 per year; the boiler room area was reduced from 80 square meters to 28 square meters.
·Customer feedback:"The boiler room used to take up half a basement floor, but now it only needs one corner, and the operating noise is so low that it's almost inaudible."
Case 2: Heating system renovation at a top-tier hospital
·Project Overview: Heating AreaThe site covers 60,000 square meters and was originally equipped with three 4-ton steam boilers (which had been in operation for 12 years with an efficiency of only 78%).
·Free energy scheme:10 180kW flat stacked modular furnaces (8 in use, 2 on standby, N+2 redundancy)
·Operational results: Thermal efficiency fromThe efficiency of gas consumption increased from 78% to 108%, resulting in a 41% reduction in annual gas costs; NOx emissions decreased from 150 mg/m³ to 25 mg/m³.
·Customer feedback:"Hospitals are most afraid of heating outages, but the redundant design of the Free Energy system gives us peace of mind—even if two units fail simultaneously, the heating will not be affected."
Case 3: Central Heating in an Industrial Park
·Project Overview: Total area of the park120,000 square meters, including office buildings, factories, dormitories and other business formats.
·Free energy scheme:24 180kW flat stacked modular boilers are distributed across 3 heating stations.
·Operational effect: Distributed heating reduces heat loss in the pipe network.15%; annual gas cost savings of 2.2 million; carbon emissions reduced by 1,200 tons/year
·Customer feedback:"Distributed systems are much more flexible than centralized systems. Only the areas that need it can open a station, instead of burning through the entire campus at once."
Flat stacking technology, as a core technology platform for free energy, will continue to iterate in the future.
short term(2026-2027):
·Microchannelization of flat rectangular tubes: further reducing the cross-sectional dimensions of flat rectangular tubes and increasing the heat transfer area per unit volume to the current level.1.5 times
·Intelligent upgrade: integrationAI load forecasting algorithms automatically optimize operational strategies based on weather and historical data.
·Hydrogen compatibility: Research and development of hydrogen-blended combustion (20%H2) compatible wide-range burner, preparing for the hydrogen energy era.
Mid-term (2027-2028):
·Flat stacking+Heat Pump Coupling: Develop a coupling system between a flat stacked boiler and an air source heat pump to achieve intelligent switching between dual energy sources.
·Carbon capture integration: A small carbon capture module is integrated at the rear end of the flat stacked heat exchanger to achieve near-zero carbon emissions.
·Material Upgrade: Exploring titanium alloy flat square tubes to further improve corrosion resistance and service life.25 years+
long(2028+):
·Platformization of Flat Stacked Technology: Promoting flat stacked heat exchange structures to fields such as industrial waste heat recovery, marine boilers, and nuclear power heat exchange.
·Pure hydrogen combustion: AchievingFlat stacked boiler with 100% pure hydrogen combustion, truly zero carbon emissions.
·Digital twin: Establish a digital twin model for each boiler to enable predictive maintenance throughout its entire lifecycle.
the term | English | definition |
Flat stacking | Flat-Stack | A heat exchanger structure using rectangular cross-section flat square tubes in a precise three-dimensional stack. |
Ample burner | Wide-Tolerance Burner | Free Energy's independently developed planar premixed burner has a wide air-fuel ratio adaptability range. |
Fully premixed combustion | Full Premix Combustion | Combustion method in which fuel gas and air are completely mixed before entering the combustion chamber. |
1:10 adjustment ratio | 1:10 Turndown Ratio | Boilers canContinuous and stable operation within 10%-100% of rated power range |
LMTD | Log Mean Temperature Difference | Logarithmic mean temperature difference, a core parameter in heat exchanger design |
WOOD | Pitting Resistance Equivalent Number | Pitting corrosion equivalent is an indicator used to assess the pitting corrosion resistance of stainless steel. |
NOx | Nitrogen Oxides | Nitrogen oxides, a major air pollutant emitted by boilers |
TCO | Total Cost of Ownership | Total lifecycle cost, including initial investment, operation, maintenance, compliance, etc. |
·GB 20665-2015 Energy Efficiency Limits and Energy Efficiency Grades for Household Gas-fired Instantaneous Water Heaters and Gas-fired Heating Boilers
·GB/T 10180-2017 Test Procedure for Thermal Performance of Industrial Boilers
·GB 13271-2014 Emission Standard for Air Pollutants from Boilers
·DB11/139-2015 Beijing Municipal Standard for Air Pollutant Emissions from Boilers
·GB/T 16507-2013 Water Tube Boilers
·GB/T 2423.10-2019 Environmental Testing - Part 2: Test Methods - Test Fc: Vibration (Sine)
·TSG 11-2020 Boiler Safety Technical Regulations
The technical data and performance indicators contained in this white paper are based on internal testing by Free Energy and reports from third-party testing agencies, and are for reference only. Actual operating results may vary due to factors such as installation conditions, operating conditions, and maintenance levels. Free Energy reserves the right to improve the product technical parameters without prior notice.
This white paper is copyrighted by Foshan Ziyou Energy Electric Co., Ltd. Reproduction, dissemination, or citation in any form is prohibited without written authorization.
— End of White Paper —