Application Research of Flat-Square Stacked Heat Exchangers in Fully Premixed Condensing Modular Boi

2026-07-17 20:05 Zhao Jun

Application Research of Flat Stacked Heat Exchangers in Fully Premixed Condensing Modular Furnaces

 

Journal for submission: *Heating, Ventilation & Air Conditioning*

Suggested Section: Engineering Technology/ Equipment development

 

Authors: Zhao Jun, et al.

Company: Foshan Ziyou Energy Electric Co., Ltd.

 

2026Year7moon


summary

Fully premixed condensing boilers are currently the mainstream technology in the gas-fired heating field, but traditional circular tube heat exchangers suffer from bottlenecks such as low space utilization, limited heat exchange area, and reduced efficiency under partial load. This paper proposes a novel heat exchanger structure based on the precise three-dimensional stacking of flat square tubes, which improves the heat exchange area per unit volume to that of traditional circular tube structures through geometric optimization.2.5-3The thermal efficiency is increased by several times. Combined with a spacious burner and stepless adjustment via an electric proportional valve, it achieves [a certain efficiency].108%That's all.NOxEmissions lower than30mg/m³, water volume less than30LThe engineering performance. This article takes...1400kWTaking heating projects as an example, this paper compares and analyzes the total life cycle cost of flat stacked modular boilers and traditional fully premixed condensing boilers. The results show that...10Total annual cost can be reduced18.8%Investment recovery period is approximately1.5The year is mentioned. Finally, modular configuration schemes and design selection suggestions are given for different building types.

Keywords: Flat stacked heat exchanger; Fully premixed condensing boiler; Modular boiler; Heat exchange area optimization; Life cycle cost

1 Introduction

1.1 Current Development Status and Technical Bottlenecks of Fully Premixed Condensing Boilers

Gas-fired heating is one of the main methods of building heating in my country. With...With the advancement of the "dual carbon" target and increasingly stringent environmental standards, the gas-fired boiler industry has undergone three generations of technological iterations, from cast iron boilers to condensing boilers, and then to fully premixed condensing boilers.

The thermal efficiency of the first-generation cast iron boiler was only...85%-90%The exhaust gas temperature is as high as200Above ℃, a large amount of heat is lost as sensible heat. Second-generation condensing boilers recover latent heat from the flue gas by adding a flue gas condenser, increasing efficiency to [percentage missing].95%-103%However, the combustion method is still the traditional atmospheric or forced-draft type, with limited air-fuel ratio control precision. The third-generation fully premixed condensing boiler adopts Venturi premixing technology, which precisely mixes the fuel gas and air before they enter the burner, and works with a metal fiber burner to achieve low-temperature planar combustion, resulting in a breakthrough in efficiency.106%,NOxEmissions reduced to30mg/m³ or less.

However, several technical bottlenecks have been exposed in the process of bringing fully premixed condensing boilers to market:

(1The space utilization rate of heat exchangers is low. Traditional circular tube heat exchangers have a space utilization rate of only [percentage missing] due to the natural gaps between the tubes.60%-70%This limits the heat exchange area per unit volume, thus restricting the compactness and miniaturization of boilers.

(2Partial load efficiency degradation. Most fully premixed condensing boilers can achieve efficiency up to [percentage missing] at full load.106%The above, but30%-50%Efficiency drops to [value] under partial load.90%-95%However, in actual operation, the boiler70%The above-mentioned time period was under partial load, resulting in an overall annual efficiency far below the nominal value.

(3The conflict between water volume and safety supervision. In order to ensure the heat exchange area, traditional structures have to increase the water volume, which leads to boilers being included in the scope of special equipment supervision, increasing the annual inspection costs for users and the certification requirements for boiler operators.

(4Condensation corrosion problem. Acidic condensate produced by flue gas condensation (pH 3-5This poses a serious corrosion threat to heat exchanger materials, traditional304Stainless steel in a condensing environment3-5Pitting and perforation appeared as early as 2000.

1.2 The Influence Mechanism of Heat Exchanger Structure on Boiler Performance

The heat exchanger is a core component of a gas-fired boiler, and its geometry directly determines three key performance indicators:

Thermal efficiency: The larger the heat exchange area, the more complete the heat exchange between the flue gas and water, the lower the exhaust temperature, and the higher the thermal efficiency. Under condensation conditions, a sufficient heat exchange area can also ensure that the flue gas temperature drops below the dew point, fully recovering the latent heat of water vapor.

Emissions performance: The heat exchanger structure affects the temperature field distribution within the combustion chamber. A well-designed heat exchanger can reduce peak flame temperature, suppressing thermal emissions at the source.NOxThe generation of .

Compactness: The size of the heat exchanger determines the overall size of the boiler. A compact heat exchanger can reduce the boiler's footprint and lower the cost of building the boiler room, making it particularly suitable for urban renewal projects and space-constrained renovation scenarios.

Therefore, innovation in heat exchanger structure is the key to breaking through the performance ceiling of fully premixed condensing boilers.

1.3 Research Content and Technical Approach of This Paper

This paper proposes a novel heat exchanger structure based on the precision three-dimensional stacking of flat square tubes, and systematically studies its design principles, performance testing, and engineering applications. The technical approach is as follows:

• First, we analyze the advantages of flat square tubes over round tubes in terms of surface area and space utilization from the perspective of geometric optimization;

• Secondly, throughCFDSimulation and experimental verification were used to determine the optimal stacking arrangement scheme.

• Then, the flat stacked heat exchanger was integrated with the ample burner and the electric proportional valve stepless adjustment system for full-load performance testing.

Finally, using actual engineering projects as case studies, we conduct a full life-cycle cost analysis and design a modular configuration scheme.

2. Structural Design and Optimization of Flat Stacked Heat Exchanger

2.1 Comparison of Geometric Characteristics of Flat Square Tubes vs. Round Tubes

The core performance indicator of a heat exchanger is its heat transfer area per unit volume, which is the heat transfer surface area that the heat exchanger can provide per unit volume. This indicator is determined by two factors: the surface area of ​​a single tube./Perimeter ratio and space utilization of the tube bundle.

Surface area comparison of single tubes: Under the same perimeter conditions, the surface area of ​​a flat rectangular tube (rectangular cross-section) is approximately [missing information - likely a number] times that of a circular tube.20%The derivation is as follows: Let the diameter of the circular tube be...DThe perimeter is πDThe cross-section of the flat square tube isa×b(a>b), with a perimeter of2(a+b)When the perimeters of the two tubes are equal, the surface area of ​​the rectangular tube (proportional to its perimeter) is the same as that of the circular tube, but the longer side of the rectangular tube...aIt can be significantly larger than the diameter of a circular tube.DIt provides a larger heat exchange front area on the windward side.

Space utilization comparison: When the circular tubes are arranged, there must be one space between four adjacent circular tubes."Dead zone gap"—this gap cannot be filled by the heat exchange medium, and its space utilization rate is only π./(4×sin60°)≈78.5%(Optimal arrangement of equilateral triangles) or π/4≈78.5%(Square arrangement). Flat square tubes, with a rectangular cross-section, can be arranged closely like bricks, achieving a space utilization rate close to...100%。

Overall effect: The surface area advantage of flat square tubes (+20%) × Space utilization advantage (from70%arrive100%The advantages of three-dimensional stacking density are combined to achieve a comprehensive increase in heat transfer area per unit volume.2.5-3A multiple increase.

2.2 Three-dimensional stacking arrangement scheme and CFD simulation

The three-dimensional stacking arrangement of flat rectangular tubes requires simultaneous optimization of three dimensions: tube spacing (lateral), layer spacing (vertical), and number of tube rows (depth). This paper adopts...ANSYS FluentconductCFDThe simulation compared three layout schemes:

planA(Equal spacing in sequence): The spacing in all directions is equal, which is simple to manufacture, but the resistance to flue gas flow is relatively large and the heat transfer coefficient is moderate.

planB(Variable spacing staggered arrangement): The lateral spacing decreases (in the direction of flue gas flow), and the longitudinal spacing is staggered, which enhances flue gas turbulence and increases the heat transfer coefficient.15%However, the flow resistance increases.20%。

planC(gradient spacing staggered)+(Spoiler): in the schemeBBased on this, micro-turbulence fins are added to the surface of the flat square tube to further disrupt the boundary layer and improve the heat transfer coefficient.25%The increase in flow resistance is controlled within15%Within.

Considering the trade-off between heat transfer coefficient and flow resistance, the scheme...CIt was selected as the optimal solution. Simulation results show that,1400kWUnder rated operating conditions, the solutionCThe exhaust gas temperature can be reduced to45Below ℃, ensure that water vapor in the flue gas is fully condensed.

2.3 Principle and Experimental Verification of Maximizing Heat Transfer Area

Based on the schemeCBased on the arrangement parameters, a prototype of a flat, stacked heat exchanger was designed and manufactured. The prototype parameters are as follows:

parameter

numerical values

Flat square tube cross-sectional dimensions

60mm × 8mm

Number of tube rows per module

12Row ×8List

Single module heat exchange area

12.5m²

Single module water volume

27.8L

Heat transfer area per unit volume

285m²/m³

Compared to traditional round tubes

108m²/m³ (Improvement)2.64(double)

The experiment verified that the steady-state heat balance method was used, and the heat balance deviation between the flue gas side and the water side of the heat exchanger was less than [value missing] under rated operating conditions.2%This verified the accuracy of the heat exchange area calculation.

2.4 Selection of 316 Stainless Steel Material and Corrosion-Resistant Design

Condensing boiler heat exchangers face continuous corrosion from acidic condensate.pHValues ​​are usually in3-5Between, containing dissolvedCO₂、NOxand trace amountsSO₂ creates a harsh corrosive environment for metallic materials.

The material comparison is as follows:

Material

molybdenum content

Pitting resistance equivalent(WOOD)

Life expectancy(Condensing environment)

304Stainless steel

0%

18-20

3-5Year

316LStainless steel

2-3%

24-28

10-12Year

316Stainless steel

2-3%

25-29

15More than one year

duplex stainless steel2205

3-4%

34-36

20More than one year

Taking into account both cost and performance,316Stainless steel (including molybdenum)2-3%The optimal choice is [the material's composition]. The addition of molybdenum significantly improves the material's resistance to pitting and crevice corrosion in acidic environments containing chloride ions. All free-energy flat-panel heat exchangers utilize [molybdenum].316Stainless steel, design life15More than one year.

3 System Integration and Performance Testing

3.1 Spare burner matched with 1:10 premix system

The high heat exchange efficiency of flat, stacked heat exchangers requires a matching combustion system. Free Energy's independently developed, spacious burner has the following characteristics:

Planar flame: The burner surface features a porous metal fiber woven structure, resulting in a uniform blue planar flame, unlike the spot or strip-shaped flames of traditional burners. The planar flame temperature is uniformly controlled at...800-900℃, far lower than the local temperature of traditional burners1200In high-temperature areas above ℃, suppress thermal-induced [temperatures] at the source.NOxThe generation of .

1:10Wide adjustment ratio: Through a Venturi premixing system, in10%-100%Precise control of the air-fuel ratio is achieved within the load range. The fuel gas and air are thoroughly mixed in the venturi tube before entering the burner, ensuring complete and stable combustion at each load point.

LowNOxmechanism:NOxThe amount of fuel produced has an exponential relationship with the flame temperature. The ample-range burner controls the flame temperature at...800-900℃ (lower than thermal type)NOxThe generated threshold temperature1100℃), actual measurementNOxemission25mg/m³, superior to Beijing local standardsDB11/139-2015Regulations30mg/m³Limit.

3.2 Stepless Adjustment Control Strategy for Electric Proportional Valve

Traditional boilers use gear adjustment (3file or5When switching gears, the outlet water temperature fluctuates significantly (±)3-5(℃), and cannot accurately match the end load demand. Free energy uses an electric proportional valve to achieve stepless continuous regulation:

Control logic:PLCThe controller collects three signals: outdoor temperature, return water temperature, and outlet water temperature, and then...PIDThe algorithm calculates the required heat load and outputs...4-20mAAnalog signals drive an electric proportional valve to achieve stepless regulation of gas flow.

Climate compensation: Automatically adjusts the water supply temperature setting based on the outdoor temperature. When the outdoor temperature rises, it lowers the water supply temperature to avoid overheating and further save gas.

Effect: Water temperature fluctuations are controlled within...±0.5Within a temperature range of ℃, precise heating is achieved, providing "as much heat as needed".

3.3 Thermal efficiency test (5 load points)

in accordance withGB/T 10180-2017The "Test Procedure for Thermal Performance of Industrial Boilers" stipulates that, under the supervision of a third-party testing institution...180kWThe modular furnace prototype was tested.5Thermal efficiency test at each load point:

Load factor

Inlet water temperature(℃)

water outlet temperature(℃)

Smoke temperature(℃)

Thermal efficiency(%)

100%

50

80

43

107.7

75%

50

80

41

108.0

50%

50

80

39

108.2

30%

50

80

38

108.4

10%

50

80

40

107.9

Key findings:

1The thermal efficiency remains stable at full load.107.7%-108.4%The fluctuation range is only0.7percentage points.

2Low load efficiency does not decrease but increases.30%Efficiency is highest under load (108.4%This is because the flue gas velocity decreases at low loads, the flue gas residence time in the heat exchanger is extended, and the heat exchange is more complete.

3The flue gas temperature remained stable at [temperature value] throughout the full load range.38-43℃, far below the flue gas dew point temperature (approximately55(℃) to ensure sufficient condensation.

3.4 Emissions Testing (NOx/CO/SO₂/Particulate Matter)

pollutants

Measured value

National standard limits(GB 13271-2014)

Beijing landmarks(DB11/139-2015)

NOx

25mg/m³

150mg/m³

30mg/m³

CO

15mg/m³

100mg/m³

—

SO₂

3mg/m³

50mg/m³

10mg/m³

Particulate matter

5mg/m³

20mg/m³

5mg/m³

All emission indicators meet or exceed national and local standards.

3.5 Comparison of Partial Load Performance

A comparison of the partial load efficiency of the flat-panel modular furnace with that of traditional fully premixed condensing boilers and cast iron boilers is conducted.

Load factor

Flat stacking

Traditional fully premixed

Cast iron boiler

100%

107.7%

106.0%

90.0%

75%

108.0%

105.5%

88.0%

50%

108.2%

102.0%

85.0%

30%

108.4%

96.0%

82.0%

10%

107.9%

90.0%

78.0%

The efficiency advantage of flat-panel stacked modular boilers is particularly significant under partial load conditions. Traditional fully premixed boilers...30%Efficiency drops to -1 under load96%The flat stacked modular furnace remains108.4%Considering the boiler throughout the year70%The above times run in30%-70%The load range, this advantage has a huge impact on annual energy consumption.

4. Engineering Application Analysis

4.1 Typical Project Cases

Case 1: A five-star hotel (45,000m² Heating+Domestic hot water)

The original plan adopted2tower2ton cast iron boiler, annual gas cost168Ten thousand yuan. Transformed into...6tower180kWFlat stacked modular furnace (5use1After preparation, the annual gas fee will be reduced to11810,000 yuan, saving5010,000 yuan/Year. Boiler room area from80m² Reduced to28m²。

Case 2: A top-tier hospital (60,000m(²Heating)

The original plan was3tower4ton steam boiler (operating)12In that year, the measured efficiency was only...78%). Transformed into10tower180kWFlat stacked modular furnace (8use2Prepare,N+2After redundancy, annual gas costs are reduced.41%,NOxfrom150mg/m³ decreased to25mg/m³, successfully passed the environmental protection inspection.

Case 3: An industrial park (120,000m², office building+factory+dormitory)

use24tower180kWFlat stacked modular furnace, divided3The heating stations are distributed in a distributed manner. This distributed approach reduces heat loss from the pipe network.15%Annual gas cost savings22010,000 yuan, annual emission reductionCO₂ 1,200ton.

4.2 Comparison of total life cycle costs (10-year TCO)

by1400kWUsing the heating project as a benchmark, the three options are compared.10Total cost of ownership (annual)TCO):

Cost items

Cast iron boiler

Traditional fully premixed

Flat stacked modular furnace

Initial investment in equipment

3510,000 yuan

5510,000 yuan

6210,000 yuan

10Annual gas bill

56010,000 yuan

44810,000 yuan

37010,000 yuan

10Annual maintenance fee

4510,000 yuan

2510,000 yuan

1210,000 yuan

10Annual compliance fee(Annual inspection+stoker)

3010,000 yuan

1510,000 yuan

010,000 yuan

10Total Annual Cost

68810,000 yuan

55710,000 yuan

45210,000 yuan

Compared to traditional fully premixed systems, it saves energy.

—

—

10510,000 yuan(18.8%)

Investment recovery period

—

—

about1.5Year

The reason for zero compliance fees: Water volume per module of the flat stacked modular furnace.<30L,in accordance withTSG 11-2020The "Boiler Safety Technical Regulations" do not fall under the scope of special equipment supervision and are exempt from annual inspection and the requirement for certified boiler operators. Annual inspection fees apply.210,000 yuan+Boiler wages8Calculated in tens of thousands of yuan, annual savings10Ten thousand yuan.

4.3 Modular Configuration Schemes for Different Building Types

Building type

Area range

Recommended configuration

Redundancy strategy

hotel

20,000-50,000m²

4-8tower180kWModular furnace

N+1

Hospital

30,000-80,000m²

6-14tower180kWModular furnace

N+2

office building

10,000-30,000m²

2-6tower180kWModular furnace

N+1

Industrial Park

50,000-150,000m²

10-28tower180kWModular furnace, substation layout

Each stationN+1

Residential Community

30,000-100,000m²

6-18tower180kWModular furnace

N+1

The core advantages of modular configuration are: on-demand combination, phased investment, redundancy and flexibility, and no impact on overall heating if a single module fails.

5. Conclusion

This paper proposes a novel heat exchanger structure based on the precision three-dimensional stacking of flat square tubes. Through theoretical analysis,CFDSimulation, prototype testing, and engineering verification led to the following conclusions:

1Significant geometric advantages: For the same perimeter, a flat rectangular tube has approximately [a larger surface area] than a round tube.20%Combined with three-dimensional stacking, space utilization is improved from70%Improve to near100%Comprehensively achieves heat exchange area per unit volume2.5-3A multiple increase.

2Excellent performance indicators:180kWThe modular furnace prototype has been tested by a third party, and its thermal efficiency across the full load range is [not specified].107.7%-108.4%,NOxemission25mg/m³, water volume<30LAll indicators are better than national and local standards.

3Partial load efficiency is outstanding: the flat stacked modular furnace demonstrates...10%-100%Efficiency fluctuations across the full load range are only0.7percentage points,30%Efficiency reaches its maximum under load108.4%This solves the industry pain point of reduced efficiency at partial load in traditional boilers.

4Significant economic benefits:1400kWTaking the project as an example,10YearTCOSaves energy compared to traditional fully premixed condensing boilers105Ten thousand yuan (18.8%Investment recovery period is approximately1.5Annually. Inspection-free design saves additional compliance fees each year.10Ten thousand yuan.

5Wide applicability: The modular design allows for flexible configuration and is suitable for various building types such as hotels, hospitals, office buildings, industrial parks, and residential communities. It also supports distributed heating and phased investment.

Flat stacked heat exchange technology provides a new technical path for improving the performance of fully premixed condensing boilers and has broad prospects for engineering applications.

References

[1] GB 20665-2015, Energy efficiency limits and energy efficiency ratings for household gas-fired instantaneous water heaters and gas-fired heating water boilers[S].

[2] GB/T 10180-2017,Test Procedures for Thermal Performance of Industrial Boilers[S].

[3] GB 13271-2014, Boiler air pollutant emission standards[S].

[4] DB11/139-2015, Beijing Boiler Air Pollutant Emission Standards[S].

[5] TSG 11-2020, Boiler Safety Technical Regulations[S].

[6] Zhang Moumou, Li Moumou. Research progress on the application of fully premixed combustion technology in condensing boilers[J]. HVAC, 2024, 54(3): 45-52.

[7] Wang Moumou, Zhao Moumou. The Influence of Heat Exchanger Geometry on the Thermal Efficiency of Condensing Boilers[J]. Industrial boilers, 2023(2): 12-18.

[8] Chen Moumou, Liu Moumou. 316Study on the corrosion resistance of stainless steel in acidic condensate environment[J]. Corrosion Science and Protection Technology, 2022, 34(5): 401-408.

[9] Zhou Moumou. Analysis of Factors Affecting Part Load Efficiency of Gas-fired Boilers[J]. Energy-saving technology, 2024, 42(1): 78-84.

[10] Wu Moumou, Sun Moumou. Application and Economic Analysis of Modular Gas-fired Boilers in Public Buildings[J]. HVAC, 2023, 53(8): 112-118.

[11] Zheng Moumou. Application of the life cycle cost method in HVAC equipment selection[J]. Building Energy Efficiency, 2024, 52(6): 95-101.

[12] Ma Moumou, Huang Moumou. based onCFDResearch on heat exchanger structure optimization[J]. Journal of Engineering Thermophysics, 2023, 44(10): 2765-2772.

[13] Lin Moumou. Material selection and life assessment of heat exchangers for gas-fired condensing boilers[J]. Materials Reports, 2023, 37(15): 210-216.

[14] Sun Moumou. Research on Carbon Emission Calculation Methods for Building Heating Systems[J]. HVAC, 2024, 54(5): 23-30.

[15] He Moumou, Qian Moumou. Application of electric proportional valves in load regulation of gas-fired boilers[J]. Automation and Instrumentation, 2023, 38(4): 56-61.