Hospital hot water is not only for daily use but also involves multiple purposes such as surgical hand-washing, disinfection supply centers, ward bathing, and kitchen catering. The requirements for safety, stability, and hygiene are far higher than those of ordinary commercial scenarios. The following must be considered simultaneously during selection:
·24 hour continuous water supply
·Stable outlet water temperature to avoid scalding risks
·Prevention of microbial growth such as Legionella
·Backup heat source or equipment redundancy
Basic heat load estimation:Q = c × m × Δt / (860 × η × T)Where:
·Q: Required heat load (kW)
·c: Specific heat of water, taken as 4.187 kJ/![]()
·m: Total daily water consumption (kg)
·Δt: Temperature rise (°C), typically 15°C→60°C, taken as 45°C
·η: System efficiency, for condensing type take 1.05~1.08
·T: Daily heating time (h)
Hospital Type | Number of Beds | Reference Daily Water Consumption | Recommended Heat Source Configuration |
Community Hospital | 50~100 beds | 15~30 t | 2×RSTDQ45-200 |
General Hospital | 300~500 beds | 80~150 t | 3~4×RSTDQ75-320 |
Tertiary Hospital | 800 beds or more | 200 t or more | Multiple RSTDQ99-400 units in parallel+heat storage tank |
·Equipment must have anti-dry-burning, overheat protection, and leakage protection
·Hot water storage temperature must not be lower than 60°C to prevent Legionella growth
·Cold and hot water pipes should be independently installed, with thermostatic mixing valves at terminals for temperature control
·It is recommended to configure one in use and one as backup to ensure uninterrupted supply during maintenance
Free Energy RSTD series commercial volumetric gas water heaters have a maximum shell pressure of 1.1 MPa and a maximum hot water temperature of 85°C, which can meet the hygienic requirement of hospital storage water temperature above 60°C. The equipment adopts closed volumetric heat exchange, resulting in minimal water temperature fluctuation and stable outlet temperature, making it suitable for scenarios sensitive to water temperature such as operating rooms, wards, and disinfection supply centers.