Operation and Usage Manual for Fully Premixed Flat-Stacked Modular Boiler

2026-07-01 19:53 Free Energy
Fully Premixed Hot Water Modular Boiler Operation Manual.pdf




Fully premixed hot water boiler





Product Manual







Foshan Ziyou Energy Electric Co., Ltd.







Table of contents

TOC \o "1-3" \h \z HYPERLINK \l _Toc23092 1. Main Interface Button Function Description: 3

HYPERLINK \l _Toc17761 2. Machine Setup Instructions: 4

HYPERLINK \l _Toc26415 3. Timed combustion: 5

HYPERLINK \l _Toc28919 4. Administrator: 6

5. Fan parameter settings: 7

HYPERLINK \l _Toc19483 7. Super Administrator: 8

HYPERLINK \l _Toc9392 8. Administrator Backend Login Instructions: 9

9.Precautions for using gas-fired modular furnaces: 9

HYPERLINK \l _Toc10913 10. Wiring Diagram: 11

11. Installation diagram: 12
































1. Main Interface Button Function Description:                                                        

Key Name

Key Function Description

Troubleshooting

If resetting the machine resolves the problem and the system still shows abnormalities upon retesting, it is recommended to perform appropriate maintenance based on the fault codes.

Equipment start-up and shutdown

The machine's main start/stop button is green for on and red for off.

Equipment Details

Real-time monitoring of the operation of each module

Machine settings

Access the parameter settings page to set the temperature, hysteresis, and access the administrator settings, etc.

Timed combustion

Set the timed combustion function (refer to the time displayed on the screen for the time setting).


2. Machine Setup Instructions:





Function Name

Functional Parameter Description

scope

Set temperature

When combustion occurs, the main controller outputs a temperature value that reaches this value.Set temperature valueThe machine stopped burning.

30~80℃

Hysteresis temperature

The machine burned toSet temperatureWhen the set temperature is reached, combustion stops. The condition for resuming combustion is that the current temperature is less than the set temperature plus the hysteresis temperature, which equals the reheat temperature (for example, if the set temperature is 60℃, the hysteresis temperature is 10℃, the current temperature is 60℃, and the machine starts combustion when the output temperature drops to 50℃).

2~30℃

Set combustion temperature

When controlled combustion is performedIndividual control output temperature valueWhen the set temperature is reached, the machine will adjust the heating power to maintain a constant temperature.

30~80℃

Set the flue gas temperature

Combustion stops when the flue gas temperature reaches the set value. Resumption of combustion occurs when the current flue gas temperature is less than a certain value.(Set temperature -10)Reheat (for example, set to 100℃, the current temperature is 120℃, the machine starts to burn when the output temperature drops to 90℃).

30~250℃

Clock Date

Update the machine's running clock to enable it.Timed combustionTime judgment conditions


Brightness, screen saver, sleep mode

Adjust screen brightness; enable/disable screen saver notifications when not in use; enter sleep mode after five minutes of inactivity.

After 3 minutes of no touch, the screen will enter its lock screen.

Exit screensaver password: 6666;

Administrator

Manage some of the more sensitive operating parameters of the equipment.

Default password: 8888






3. Timed combustion:


                 



Click the corresponding time period to select on or off (OFF: Off; ON: On). Click the main switch for timed combustion to enable or disable the timer function (OFF: Off; ON: On).

Note: When the timer function is enabled, the temperature for the timed period is the main control combustion start/stop temperature.

administrator:




Function Name

Function Description

Water pump operation mode

"Keep switching modes"After the equipment reaches the target start-stop temperature and shuts off, the water pump continues to run.

"3-turn, 7-stop mode"After the equipment reaches the target heating temperature (°C) and shuts off, the water pump will run for 3 minutes and then stop for 7 minutes. This cycle repeats.

water tankThe water pump will shut off 60 seconds after the fire is stopped.

Sub-control number

Number of working sub-control modules

Water pressure sensor type

AD Type: Pressure sensor; Pressure detection method: [Not specified] Switch Type: Mechanical switch; None: No detection.

When a water pressure sensor is installed, if the water pressure requirement is not met during combustion, a water pressure fault will be reported.

Types of water flow switches

Start/Stop: The system only starts working when the main control flow switch interface is closed, and stops working when it is opened. The start/stop switch is displayed as open.

Control switch

When the control switch is turned off, the machine stops working; when the switch is turned on, combustion begins.

heating methods

Heatsink mode: Can be started/stopped with a maximum temperature setting of 80 degrees Celsius;

Underfloor heating mode: Start/stop temperature can be set up to 60 degrees Celsius.

Fan speed protection

When the fan speed is greater than(This setting increases the engine speed by 500)At that time, the machine reported a fan malfunction and stopped working.


Parameter settings

The maximum fan speed, ignition speed, and minimum fan speed can be set.






Fan parameter settings:




Function Name

Function Description

Current sub-control number

First select the module whose parameters you want to change, and then adjust the parameter area on the right.

Fan ignition wind speed

This setting is systemWhen ignitingThe ignition fan speed is not set correctly during ignition, resulting in a fan speed mismatch warning.


Maximum wind speed of the fan

The maximum fan speed during maximum combustion of the system is this set value.


minimum wind speed of the fan

The minimum fan speed during minimum combustion in the system is this set value.

ON / OFF

The default setting (grayed out) indicates that only the currently displayed sub-control number parameter is being set. Clicking "Show ON" will...All sub-controllers synchronizeTo the current parameter
















6. Sub-control status query:

To query the real-time operating status of the sub-controllers and control their on/off states,Top right iconTroubleshooting.

   Fan start-up display icon Water flow switch closed indicator  Normal burning flame icon


7Super Administrator:

After entering the machine settings page and correctly entering the password, you will be redirected to the administrator parameter settings interface.Click on this pagebottom right cornerThe super administrator can be accessed by entering the password.Initial password: 89898989


8Administrator backend login instructions:


Initial login password:89898989After entering the correct password, press the confirmation button to enter the management backend, as shown in the image below.



9. Precautions for using gas-fired modular boilers

I. Installation and Commissioning Safety Requirements

1. This equipment is only compatible with natural gas and liquefied petroleum gas. The standard gas supply pressure is 1800~2800Pa. It is strictly forbidden to use manufactured gas, otherwise problems such as incomplete combustion, excessive exhaust gas, and equipment damage will occur.

2. The installation of the entire unit, connection of water/gas pipelines, gas tightness testing, and initial ignition and commissioning must be carried out by qualified professionals with gas equipment installation and maintenance qualifications. Users are prohibited from modifying pipelines, exhaust systems, and electrical control circuits themselves.

3. Equipment rooms and equipment rooms must be equipped with top and bottom ventilation openings. Flammable and explosive materials such as paint, thinner, cardboard boxes, and alcohol must not be stored indoors. Exhaust pipes must be sealed without damage, water accumulation, or backflow. Outdoor exhaust outlets should avoid door and window air inlets to prevent carbon monoxide backflow and poisoning.

4. The metal casing of the equipment must be reliably grounded, and the ground wire must not be connected to the water pipe or the neutral wire; the water pressure of the water system should be maintained at 0.05~0.7MPa, and an air vent valve should be installed at the highest point of the pipeline to purge the air inside the pipeline before the equipment is put into use.

5. The main gas pipeline must be equipped with an independent manual ball valve and a gas filter. After installation, pressure test and leak detection must be performed. Ignition and trial operation can only be carried out after confirming that there is no leakage.

6.Because this equipment is an ultra-low volume device, it must be used with pure water (or antifreeze) with a conductivity of less than 50µm as circulating heating water during use. Damage to the equipment caused by not using pure water (or antifreeze) that meets this requirement is not covered under warranty.

II. Startup and Operation Procedures

1. Before starting the machine, check the following items: the system water pressure is normal, there is no water or gas leakage in the pipeline, the gas ball valve is fully open, the water flow switch and temperature probe are securely connected and not loose.

2. Heating modes must be strictly differentiated by set temperature: the maximum temperature for underfloor heating mode should not exceed 60℃, and the maximum temperature for radiator heating mode should not exceed 80℃. Long-term operation above the set temperature is strictly prohibited to prevent pipe aging due to high temperature and water vaporization, which could cause pipe bursts.

3. In unattended heating scenarios, it is recommended to turn on the water pump circulation mode and utilize the equipment's low-temperature lock function to prevent pipes from freezing and cracking in winter.

4. If you smell gas indoors, immediately stop the gas supply, close the main gas valve, and open the windows for ventilation. Do not turn on or off lights or sockets, or use open flames. Go to a safe outdoor area and contact gas maintenance personnel.

III. Parameter Permission Management Precautions

1. The base temperature and timed combustion parameters can be adjusted independently by the on-site operator.

2. The underlying operating parameters such as the fan ignition wind speed, maximum/minimum wind speed, flue gas protection temperature, and fan speed protection must not be modified arbitrarily. Incorrect parameters may cause serious malfunctions such as flameout, deflagration, and fan burnout.

3. Exit screen saver password 6666 is only used to wake up the display and does not grant permission to modify device parameters.

IV. Routine Inspections and Regular Maintenance

1. Daily inspection items: Check for leaks in the pipeline (water, gas), for unusual noises or pungent odors in the smoke exhaust, and for fault alarm codes on the touch screen.

2. Quarterly maintenance: Clean the gas filter and purge the surface dust from the heat exchanger; Annual overhaul: Check the fan operating status, ignition electrode, temperature probe, and water pressure/flow switch sensitivity.

3. Winter antifreeze operation: For short-term shutdowns, keep the whole machine powered on and the water circuit pressurized, and use the timed water pump to circulate and prevent freezing; for long-term shutdowns (more than 7 days), close the water inlet and gas valves, drain the water from the furnace body and all pipes, and disconnect the main power supply to the equipment.

4. When the equipment reports alarms such as water flow interruption, fan failure, or over-temperature protection, first click on the fault clearing and reset button; if the fault recurs, the machine must be stopped and the power disconnected for maintenance. It is forbidden to force operation with the fault.

V. Strictly Prohibited Operational Behaviors

1. It is forbidden to block the ventilation openings and smoke exhaust outlets of the equipment, and it is forbidden to lengthen, bend, cut off or block the smoke exhaust pipes without authorization.

2. Do not directly wash electrical components such as the control box, touch screen, fan, ignition electrode, and line terminals with water.

3. Do not dry-burn without water, force ignition by short-circuiting the water flow switch, or operate under excessive water pressure for extended periods.

4. When the equipment is in combustion operation, it is forbidden to disassemble the temperature probe, wiring terminals, or gas valve assembly.

5. Personnel without professional training and minors are prohibited from accessing the administrator or super administrator backend to modify device operating parameters.

VI. Shutdown Operation Procedures

1. Short-term shutdown: Press the start/stop button to turn off the equipment, but keep the whole machine powered on and the water circuit filled with water, relying on the water pump circulation function to prevent freezing.

2. Long-term shutdown: Close the main gas valve and water inlet valve, drain the water from the furnace body and all pipes, and disconnect the main power supply to the equipment; before restarting, re-complete the water circuit pressure test, gas leak detection, and whole-machine ignition test.







10. Wiring diagram:              



11. Installation Diagram:








Parameter table:




model

ZYRSDL-Q99


ZYRSDL-Q150

ZYRSDL-Q180

ZYRSDL-Q200

category

Fully premixed condensing hot water unit

Fully premixed condensing hot water unit

Fully premixed condensing hot water unit

Fully premixed condensing hot water unit

Thermal efficiency

107%

107%

107%

107%

project

unit

1Module

1Module

1Module

2Module

Machine appearance

mm

778×428×1126

778×428×1126

778×428×1126

728×808×1392

machine gross weight

kg

60

80

80

130

Machine power consumption

KW/H

0.2

0.3

0.3

0.5

Rated voltage

In

220

220

220

220

Rated heat load

KW

99

150

180

200

Gas pressure

Well

1800~2800 (natural gas)

1800~2800 (natural gas)

1800~2800 (natural gas)

1800~2800 (natural gas)

Gas consumption

m³/h

≈10

≈15

≈18

≈20

Water production temperature rise 25°C

L/h

3500

5250

6125

6805

Applicable water pressure

Mpa

0.05-0.7

0.05-0.7

0.05-0.7

0.05-0.7

Heating area

㎡

600-1200

1200-1800

1500-2500

2000-3500

CO2 emissions

PPM

<100

<100

<100

<100

NOx emissions

Mg/kwh

<30

<30

<30

<30

Smoke vent

mm

φ100


φ100


φ100


φ150


hot water outlet


DN25Outer tusk

DN25Outer tusk

DN25Outer tusk

DN50flange

Gas inlet


DN25Outer tusk

DN25Outer tusk

DN25Outer tusk

DN50flange

Inlet


DN25Outer tusk

DN25Outer tusk

DN25Outer tusk

DN50flange

hot water temperature

℃

80(max)

80(max)

80(max)

80(max)



model

ZYRSDL-Q360

ZYRSDL-Q450

RGRSDL-Q720

ZYRSDL-Q1080

ZYRSDL-Q1440

category

Fully premixed condensing hot water unit

Fully premixed condensing hot water unit

Fully premixed condensing hot water unit

Fully premixed condensing hot water unit

Fully premixed condensing hot water unit

Thermal efficiency

107%

107%

107%

107%

107%

project

unit

2Module

3Module

4Module

6Module

8Module

Machine appearance

mm

728×808×1392

1000×808×1392

1248×808×1392

1770×808×1392

1248×1748×1392

machine gross weight

kg

130

400

500

700

1000

Machine power consumption

KW/H

0.5

0.7

1

1.5

2

Rated voltage

In

220

220

220

220

220

Rated heat load

KW

360

450

720

1080

1440

Gas pressure

Well

1800~2800 (natural gas)

1800~2800 (natural gas)

1800~2800 (natural gas)

1800~2800 (natural gas)

1800~2800 (natural gas)

Gas consumption

m³/h

≈36

≈45

≈72

≈108

≈144

Water production temperature rise 25°C

L/h

12250

15750

24500

36750

49000

Applicable water pressure

Mpa

0.05-0.7

0.05-0.7

0.05-0.7

0.05-0.7

0.05-0.7

Heating area

㎡

3500-4500

4000-6000

6000-9500

10000-15000

13000-20000

CO2 emissions

PPM

<100

<100

<100

<100

<100

NOx emissions

Mg/kwh

<30

<30

<30

<30

<30

Smoke vent

mm

φ150


f250

f250

f250

F300

hot water outlet


DN50flange

DN50flange

DN65flange

DN80flange

DN100flange

Gas inlet


DN50flange

DN50flange

DN50flange

DN65flange

DN80flange

Inlet


DN50flange

DN50flange

DN65flange

DN80flange

DN100flange

hot water temperature

℃

80(max)

80(max)

80(max)

80(max)

80(max)